DKG-309 AUTOMATIC MAINS FAILURE UNIT
CANBUS AND MPU VERSIONS
DESCRIPTION
The DKG-309 is a comprehensive AMF unit for single genset standby or dual genset mutual standby operations. The unit is available with MPU or CANBUS versions. The CANBUS version connects to ECU controlled electronic engines providing engine control, protection and instrumentation without extra senders. The ECU alarms are displayed in text. The unit is able to initiate modem calls and send SMS messages in fault conditions through external modem. The unit provides a comprehensive set of digitally adjustable timers, threshold levels, input and output configurations, operating sequences and engine types. All programs may be modified via front panel pushbuttons, and do not require an external unit. Last 100 faults are stored in the event log file. The event log includes not only the date-time information, but also a comprehensive list of measured genset parameters at the time that the fault has occurred. The WINDOWS based RAINBOW program allows remote monitoring and control. The unit supports MODBUS protocol enabling communication with PLCs and building management systems. The MODBUS protocol is also supported through GSM and PSTN modems. The unit offers multiple language support.
FEATURES
True RMS measurements ECU connection through J1939 CAN option J1939 ECU warnings displayed as text MPU input option Dual genset mutual standby operation Event logging with time stamp and measurements Battery backed-up real time clock Built in daily / weekly / monthly exerciser Weekly operation schedule programs Field adjustable parameters RS-232 serial port Free MS-Windows Remote monitoring SW GSM and PSTN modem support GSM SMS message sending on fault MODBUS communications Multiple language support Customer logo display capability 16 Amp contactor outputs 1 Amp DC semiconductor outputs Configurable analogue inputs: 4 Configurable digital inputs: 7 Configurable digital outputs: 2 Total digital outputs: 6 I/O expansion capability Plug-in connection system
MEASUREMENTS
Generator Volts: L1-N, L2-N, L3-N Generator Volts: L1-L2, L2-L3, L3-L1 Generator Amps: L1, L2, L3 Generator KW: L1, L2, L3, total Generator pf: L1, L2, L3, total Generator Frequency Engine rpm Mains Volts: L1-N, L2-N, L3-N Mains Volts: L1-L2, L2-L3, L3-L1 Mains Frequency Battery Voltage Engine Coolant Temperature Engine Oil Pressure Fuel Level Engine Oil Temperature
DIGITAL INPUTS
The unit has 7 configurable digital inputs. Each input is fully configurable with selectable names, alarm type, polling, latching and contact type.
TECHNICAL SPECIFICATIONS
Alternator voltage: 0 to 300 V-AC (Ph-N) Alternator frequency: 0-100 Hz. Mains voltage: 0 to 300 V-AC (Ph-N) Mains frequency: 0-100 Hz. DC Supply Range: 9.0 to 33.0 V-DC Cranking dropouts: survives 0 V for 100ms. Typical Standby Current: 100 mA-DC Maximum Operating Current: 200 mA-DC (Relay outputs open) Generator/Mains Contactor Relay Outputs: 16 A / 250V DC Outputs: 1A @ 28V protected semiconductor output Charge excitation: min 2 Watts Magnetic pickup input:: 0.5 30 V-AC. Magnetic pickup frequency: 10 KHz max. Current inputs: from CTs, .../5A. Max load 0.7VA per phase. Analog input range: 0-5000 ohms. Serial port: RS-232, 9600 bauds, no parity, 1 bit stop Operating temp.: -20C (-4F) to 70 C (158F). Storage temp.: -40C (-40F) to 80 C (176F). Maximum humidity: 95% non-condensing. Dimensions: 172 x 134 x 46 mm (WxHxD) Panel Cut-out Dimensions: 151x111 mm minimum. Weight: 340 g (approx.) Case Material: High Temperature ABS/PC (UL94-V0) IP Protection: IP65 from front panel, IP30 from the rear CE Conformity reference standards: EN 61010 (safety requirements) EN 61326 (EMC requirements) UL / CSA Conformity: certificate # 20110527-E314374 UL 508, Edition 17 UL 2200, 1st Edition. UL 840 Edition 3 CSA C22.2 NO. 14 - Edition 10
ANALOG INPUTS
Engine analog inputs are provided for coolant temperature, oil pressure, oil temperature and fuel level. The inputs have programmable sensor characteristics so that they are suitable for any type and brand of sensors.
OUTPUTS
The unit provides 2 relay and 4 semiconductor outputs. 2 of them have programmable functions, selectable from a list. Any function or alarm condition may be a digital output. Using two Relay Expansion Modules, the number of relays may be increased to 22, 16 of them being volt-free contacts.
EVENT LOGGING
The unit records last 100 events with date-time stamp and a total of 18 measured parameters.
TELEMETRY AND REMOTE PROGRAMMING
The unit provides the user with large telemetry facilities via its standard RS-232 serial port, connecting either to a PC, PLC or a GSM or PSTN modem. It supports both RAINBOW and MODBUS communication protocols. The standard PC software offers local and modem operation capabilities as well as modem networking feature. The PC program is used for below purposes: -parameter upload/download -remote monitoring and control -diagnostics and analysis
LOAD ALTERNATOR
L1 L2 L3 N
FUSE FUSE FUSE FUSE FUSE
Generator Contactor Mains Contactor
L1 L2 L3 N
MAINS
L1 L2 L3 N
FUSE
Electrical Interlock
30
31 32
33 34
10
Remote Monitoring and Program Port Input-Output Extension Port
DKG-309
36 37 11 12 20 19 18 17 13
Fuel Level Sender
14
Oil Pressure Sender
15
Coolant Temp. Sender
35
16
21
22
23
24
25
26
High Temperature
27
28
Oil Temp. Sender
Emergency Stop
Program Lock
Spare - 2
+
Battery 12 / 24 V
Starter Motor
D+ Charge Alt.
Battery negative must be grounded.
Spare - 1
MPU or j1939
Fuel
Crank
R L1
R L2
Rectifier Fail
Oil Pressure
FUSE
L H
Coolant Level