CIRCUIT LOADING Non-Motor Loads
CIRCUIT BREAKER SIZE Amp* 75
C THW WIRE SIZE MAXIMUM Amps
Non-motor load any load any load
15 12 12
20 Normally smallest breaker 12 16
25 10 20
30 10 24
35 8 28
40 8 32
45 8 36
50 6 40
60 6 48
70 4 56
80 4 64
90 3 72
100 3 80
110 2 88
125 1 100
150 1/0 120
175 2/0 140
200 3/0 160
225 4/0 180
250 250 MCM 200
300 350 MCM or 2-1/0 Parallel 240
350 500 MCM or 2-2/0 Parallel 280
400 600 MCM or 2-3/0 Parallel 320
450 700 MCM or 2-4/0 Parallel 360
500 2-250 MCM Parallel 400
600 3-3/0 Parallel 480
700 3-4/0 Parallel 560
800 3-300 MCM Parallel 640
* For motor Loads multiply running current by 1.75-2.50 to get circuit breaker size as shown
in Table 2 above.